Area Sp. Mm |
Conductor Construction No./Dia In m.m. |
Cond.Dia mm |
Max. DC Resistance Ohm/Km At 20 0 C |
Insulation Thickness (Nominal) m.m. |
Cable Dia m.m |
Current Rating Amp. |
Area Sp. m.m. |
Con. Dia m.m. |
Max. DC Resistance Ohm/Km At 20 0 C |
Insulation Thickness (Nominal) m.m. |
Cable Dia. m.m. |
Cable Dia m.m. |
Approx. Current Rating Amp. |
0.50
|
16/0.20 |
0.94 |
39.00 |
0.6 |
2.2 |
4 |
25.00 |
157/.045 |
7.60 |
0.7800 |
1.20 |
10.50 |
71 |
0.75
|
24/0.20 |
1.20 |
26.00 |
0.6 |
2.5 |
7 |
35.00 |
220/0.45 |
8.70 |
0.5540 |
1.20 |
11.60 |
91 |
1.00
|
32/0.20 |
1.34 |
19.50 |
0.6 |
2.6 |
11 |
50.00 |
314/0.45 |
10.60 |
0.3860 |
1.40 |
13.90 |
120 |
1.50
|
48/0.20 |
1.64 |
13.30 |
0.6 |
2.8 |
14 |
- |
- |
- |
- |
- |
- |
- |
2.50
|
80/0.20 |
2.08 |
7.98 |
0.7 |
3.5 |
19 |
- |
- |
- |
- |
- |
- |
- |
4.00
|
56/.030 |
2.61 |
4.95 |
0.8 |
4.3 |
26 |
- |
- |
- |
- |
- |
- |
- |
6.00
|
85/030 |
3.50 |
3.30 |
0.8 |
5.6 |
31 |
- |
- |
- |
- |
- |
- |
- |
10.00
|
140/03.30 |
4.60 |
1.91 |
1.0 |
6.7 |
42 |
- |
- |
- |
- |
- |
- |
- |
16.00
|
101/0.45 |
5.90 |
1.21 |
1.0 |
8.4 |
57 |
- |
- |
- |
- |
- |
- |
- |
| NOMINAL CROSS SECTIONAL AREA OF CONDUCTOR IN mm 2 |
NOMINAL INSULATION THICKNESS IN m.m. |
MAX. OVER ALL DIAMETER OF CABLE IN m.m. |
1.0 |
0.7 |
3.20 |
1.5 |
0.7 |
3.40 |
2.5 |
0.8 |
4.20 |
4.0 |
0.8 |
4.80 |
6 |
0.8 |
5.60 |
10 |
1.0 |
7.00 |
16 |
1.0 |
8.20 |
25 |
1.20 |
10.00 |
35 |
1.20 |
11.50 |
50 |
1.40 |
13.00 |
70 |
1.40 |
15.00 |
95 |
1.60 |
17.50 |
120 |
1.60 |
19.00 |
150 |
1.80 |
21.00 |
185 |
2.00 |
23.50 |
240 |
2.20 |
26.50 |
300 |
2.40 |
29.50 |
| Conductor Area Sq. m.m |
Strands/Dia In m.m. |
Cond. Dia m.m. |
Max. DC Resistance Ohm/Km At 20 0 C |
Insulation Thickness (Nominal) m.m. |
Core Dia m.m. |
Sheath Thickness In m.m. (Nominal) 2 Core 3 Core 4 Core |
Overall Diameter In m.m. (Approx.) 2 Core 3 Core 4 Core |
Approx. Current Rating Amp. |
||||
0.50
|
16/0.20
|
0.94
|
39.00 |
0.6 |
2.2 |
2.2 |
0.90 |
0.90 |
6.4 |
6.8 |
7.5 |
4 |
| 0.75 |
24/0.20 |
1.20 |
26.000 |
0.6 |
2.5 |
2.5 |
0.90 |
0.90 |
7.0 |
7.4 |
8.1 |
7 |
1.00 |
32/0.20 |
1.34 |
19.500 |
0.6 |
2.6 |
2.6 |
0.90 |
0.90 |
7.2 |
7.7 |
8.3 |
11 |
| 1.50 |
48/0.20 |
1.64 |
13.300 |
0.6 |
2.9 |
2.9 |
0.90 |
1.00 |
7.8 |
8.3 |
9.2 |
14 |
2.50 |
80/0.20 |
2.08 |
7.908 |
0.7 |
3.5 |
3.5 |
1.00 |
1.00 |
9.2 |
9.8 |
10.7 |
19 |
4.00 |
56/.03 |
2.61 |
4.950 |
0.8 |
4.3 |
4.3 |
1.00 |
1.00 |
10.8 |
11.5 |
12.6 |
26 |
|
No. OF WIRE WIRE DIA. m.m.
|
BUNCH DIA. m.m |
Max. CR at 20 0 C Ohm/km |
Nominal Insulation THICKNESS m.m. |
Approx CORE DIA.m.m. |
6 CORE
|
7 CORE |
8 CORE
|
10 CORE |
12 CORE |
APPROX CURRENT RATING AMP. |
|||||
Sheath Thick m.m. |
O.D m.m. |
Sheath Thick m.m. |
OD m.m. |
Sheath Thick m.m. |
O.D. m.m. |
Sheath Thick m.m. |
O.D. m.m |
Sheath Thick m.m. |
O.D. m.m |
||||||
16/0.2 |
0.94 |
39.0 |
0.60 |
2.20 |
0.90 |
8.50 |
0.90 |
8.50 |
1.00 |
9.30 |
1.00 |
10.80 |
1.00 |
11.20 |
4 |
24/0.2 |
1.20 |
26.0 |
0.60 |
2.50 |
1.00 |
9.50 |
1.00 |
9.50 |
1.00 |
10.40 |
1.10 |
12.20 |
1.10 |
12.60 |
7 |
32/0.2 |
1.34 |
19.50 |
0.60 |
2.60 |
1.00 |
9.80 |
1.00 |
9.80 |
1.00 |
10.70 |
1.10 |
12.60 |
1.10 |
13.00 |
11 |
48/0.2 |
1.64 |
13.30 |
0.60 |
2.90 |
1.00 |
1.70 |
1.00 |
1.70 |
1.10 |
11.90 |
1.10 |
13.80 |
1.10 |
14.30. |
14 |
80/0.2 |
2.08 |
7.98 |
0.70 |
3.50 |
1.10 |
12.70 |
1.10 |
12.70 |
1.20 |
14.10 |
1.30 |
16.60 |
1.30 |
17.20 |
19 |
56/0.3 |
2.61 |
4.95 |
0.80 |
4.30 |
1.20 |
15.30 |
1.20 |
15.30 |
1.30 |
16.90 |
1.40 |
20.0 |
20.0 |
20.70 |
26 |
|
No. OF WIRE WIRE DIA. m.m.
|
BUNCH DIA. m.m |
Max. CR at 20 0 C Ohm/km |
Nominal Insulation THICKNESS m.m. |
Approx CORE DIA.m.m. |
14 CORE
|
16 CORE |
19 CORE
|
37 CORE |
APPROX CURRENT RATING AMP. |
||||
Sheath Thick m.m. |
O.D m.m. |
Sheath Thick m.m. |
OD m.m. |
Sheath Thick m.m. |
O.D. m.m. |
Sheath Thick m.m. |
O.D. m.m |
||||||
16/0.2 |
0.94 |
39.0 |
0.60 |
2.20 |
1.10
|
12.00
|
1.10
|
12.60
|
1.10
|
13.20
|
1.20 |
17.80
|
4 |
24/0.2 |
1.20 |
26.0 |
0.60 |
2.50 |
1.10
|
13.30
|
1.20
|
14.20
|
1.20
|
14.90
|
1.20
|
19.90
|
7 |
32/0.2 |
1.34 |
19.50 |
0.60 |
2.60 |
1.10
|
13.70
|
1.20
|
9.80 |
1.30
|
15.60
|
1.40
|
21.00
|
11 |
48/0.2 |
1.64 |
13.30 |
0.60 |
2.90 |
1.20
|
15.20
|
1.20
|
1.70 |
1.30
|
17.10
|
1.40
|
23.20
|
14 |
80/0.2 |
2.08 |
7.98 |
0.70 |
3.50 |
1.30 |
18.10
|
1.40
|
12.70 |
1.40
|
20.30
|
1.50
|
27.60
|
19 |
56/0.3 |
2.61 |
4.95 |
0.80 |
4.30 |
1.40
|
21.80
|
1.50 |
23.20
|
1.50
|
24.50
|
1.60
|
33.50
|
26 |